Customization: | Available |
---|---|
Color: | Grey |
Core: | Aluminium or Copper |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1 | Conductor size | mm2 | 70 | 95 | 185 |
2 | Diameter over conductor, nominal | mm | 9.3-10.2 | 11.6 | 16.4 |
3 | Thickness of dielectric | mm | 3.4 | 3.4 | 3.4 |
Nominal | |||||
Minimum at a point | mm | 2.96 | 2.96 | 2.96 | |
4 | Diameter over insulation, nominal | mm | 16.1-17.0 | 21.3 | 25.9 |
5 | Diameter over semi-conducting | mm | 18.1-19 | 23.3 | 27.9 |
core screen, nominal | |||||
6 | Thickness of copper tape nominal | mm | 0.15 | 1.15 | 2.15 |
7 | Thickness of sheath | mm | 1.8 | 1.8 | 1.8 |
Nominal | |||||
Minimum at a point | mm | 1.43 | 1.43 | 1.51 | |
8 | Catenary size | mm2 | 50 | 50 | 70 |
9 | Overall diameter of bundle, nominal | mm | 55.7 | 67.8 | 79.2 |
10 | Nominal mass | kg/m | 2.64 | 3.25 | 4.65 |
1 | Catenary size | mm2 | 50 | 70 |
2 | Number of Wires | 7 | 7 | |
3 | Wire Size(diameter) | mm | 3.0 | 3.6 |
4 | Minimum Tensile Strength of each Wire | kN | 9.26 | 13.13 |
5 | Elongation at break, minimum | % | 3.5 | 4.0 |
6 | Thickness of protective covering | |||
Nominal | mm | 1.2 | 1.2 | |
Minimum at a point | mm | 0.96 | 1.96 | |
7 | Impulse withstand voltage 1.2/50μs | 21kv/5min | 21kv/5min |